i2500-18 iFlex® Flexible Current Probes Be ready for anything.
The Fluke iFlex flexible current probes expand the measurement range of the select Fluke meters to 2500 A ac while providing the ultimate measurement flexibility. The iFlex probes connect directly to the meter, displaying current measurements without error prone scaling factors. The 1.8 m (6 ft) cord allows separation between the measurement location and the clamp meter making it easier to view the display. The large loop size and thin cross section allow measurement of awkward sized conductors and improved wire access in crowded spaces. Available in 25 cm (10 in) and 45 cm (18 in) sizes.
Safety Conformance
IEC/EN 61010-1:2001, 1000V CAT III, 600V CAT IV
SR.
Fluke CODE
Price In Rs.
1
i2500-18
10,300
Specifications
i2500-18 and i2500-10
Range
Resolution
Accuracy
AC Current*
2500 A
0.1 A
3% ± 5 digits**
Frequency*
500 Hz
0.1 Hz
0.5% ± 5 digits
External magnetic
field rejection
(with cable >10 cm from the coupling)
40 dB
Inrush*
•
Safety rating
CAT III 1000 V, CAT IV 600 V
*When used with compatible Fluke meter. Accuracy stated includes probe and meter accuracy.
** For position accuracy at non-optimum positions, see Position sensitivity specifications table “A
Position sensitivity specifications
Distance from optimum
i2500-10
i2500-18
Additional iFlex error
A
0.5 in (12.7 mm)
1.4 in (35.6 mm)
± 0.5%
B
0.8 in (20.3 mm)
2.0 in (50.8 mm)
± 1.0%
C
1.4 in (35.6 mm)
2.5 in (63.5 mm)
± 2.0%
Measurement uncertainty assumes centralized primary conductor at optimum position, no external electrical or magnetic field, and within operating temperature.